History
Since 1889, many individuals and organizations have
attempted to find the correct ampacity for conductors
so they would not overheat and ruin the insulations.
In 1889 Kennelly published one of the first tables
listing 46 amperes as the ampacity of a number 10
conductor. In 1890 Fisher listed 19.1 amperes, and
in 1894 the insurance industry listed 20 amperes as
the ampacity for the same conductor. But that was
not the end of it. By 1937 there were 16 ampacities
discovered for the same size conductor. In 1938 Samuel
J. Rosch, an associate member of the American Institute
of Electrical Engineers and the manager of insulated
products development for the Anaconda Wire and Cable
Company, conducted a thorough investigation to find
the correct ampacities for all the standard size conductors
used at that time. To establish the maximum prolonged
operating temperature for insulations, he performed
aging and elongation tests in environmental ovens.
He built a structure, wired it, embedded thermocouples
in the conductors, and applied voltages and measured
the ampacities and temperatures. He published his
findings in a paper titled, "The Current-Carrying
Capacity of Rubber-Insulated Conductors" delineating
the results of his experiments. His work resulted
in a table XI that became Table 310-16 of the National
Electrical Code. Rosch's original table was based
on an ambient temperature of 30 degrees centigrade
and a conductor temperature of 50 degrees centigrade
for code grade rubber, the type of insulation used
in those days. If we convert the ampacities in table
XI to 60 degrees centigrade using the formula given
in note 1 to tables 310-69 through 310-84, setting
delta TD equal to 0 (delta TD is for high voltages:
we are only concerned with 600 volts and under), and
rounding off to the nearest 5 amperes, we can calculate
the ampacities for 60 degree insulations as found
in the first column of table 310-16. Likewise, the
same calculation can determine the the ampacities
for the 75 degree and 90 degree columns in table 310-
16.
Faults with Table 310-16
There are three very important deficiencies in Rosch's
paper. First, he did not investigate the effects of
proximal heating from adjacent conduits, ducts, and
duct banks. Secondly, his experiments were only for
above ground installations. Thirdly, the heat produced
by high voltages was not investigated. But for most
applications when load calculations are performed
according to Article 220, there is enough safety margin
built in to preclude any problems. To explain this,
a fine print note was added to section 310-15(a) in
the 1990 NEC stating that Tables 310-16 through 310-19
are application tables that are for use in determining
conductor sizes on loads calculated in accordance
with Article 220. When calculating loads per article
220 a substantial safety margin is included as opposed
to some engineering calculations that calculate the
"actual" load.
The deficiencies to Table 310- 16 became a problem
in the 1950's when Americans began installing very
large air conditioning systems in the the larger buildings,
using underground service laterals run in massive
underground duct banks. In cases where engineers performed
load calculations using engineering methods in place
of Article 220, and used Table 310-16 to determine
the size of conductors, conductors overheated and
burned open, especially the conductors located near
the center of the duct banks. Rosch used a basic heat
transfer equation with the addition of a term "n"
for the number of conductors in the same cable or
raceway. But there were no terms in his equation to
adjust the ampacity for heat that came from adjacent
ducts and duct banks, or for the differences for heat
dissipation in an underground installation. Later
calculations using the Neher-McGrath equation found
in 310-15(b) of the NEC would determine that the center
conductors in a 3 by 3 duct banks must be derated
to almost 60 percent because of the proximal heating
effect from adjacent ducts and duct banks.
To develop a more accurate method of finding the
ampacity of conductors in underground installations
two cable engineers, in 1957, developed the Neher-McGrath
equation found in 310-15(b) of the NEC.